Design Data Page 1 of 1 According to details received from client our input data is: Subject Q Emergency Vent Value 52.6 Qu 52.6 mhr Flash point above 37.8°C Design pressure 15 mbarg Set Pressure 14 mborg Working Pressure 7.5 mbarg Tank Dia 12.5 In Tank Height 1141 Wetted Surface Area 358.7 m2 Venting Requinment(for air) 19910.0 Nm/hr Venting Requirment(for N) 20643 Nm/hr Remarks Filling rate Pump out rate Acc to Datasheet (Ace to data sheet) and is equal to 152.96 mm water 142.76 mm water (Ace to data sheet) and is equal to 76.48 mm water Acc to Datasheet Acc to Datasheet A-Dxnx9.14 As per AP12000,Table 38 based on 3034-08-ED-SE-CAL-VP-0226-0004-86 For 20in Emergency Vent, Flow rates are obtained from below diagram 22/2/2015 RV04 (Fig.3800 Persian GPE.Co Catalog) Flow Capacity According to Diagram Over Pressure 1 Pressure 142.76 mm Water Flow 23000 NCMPH 1.4 199.86 mm Water 27000 NCMPH Remarks Based on set pressure Based on 1.4 time of pressure (based on AP12000 „pas 33at C.2.31 and page 37) Emergency Vent Pressure - Flow Graph Pressure Flow Graph with 40% Over Pressure Flow Rate (Normal Cubic meters per hour* 1000) 70 60 50 40 30 20 10 289 2 24in 20in -FIO 16in -F16 -F20 -F24* 10in 50 100 150 200 250 300 350 400 450 500 550 600 650 Set Pressure (MM W.G.) x1.40 Over Pressure 700 Due to the results, our proposal is 1 set of EV (20in) for each tank (TK0801/5801)